Appendix C. System Controller Messages

Tables C-1 through C-4 list messages that can appear in the System Controller's event history log.

Table C-1. System Events—Immediate Power-Off

Error Message

Failure Area/Possible Solution

POKA FAIL

The System Controller detects a power supply fault and initiates the power-off sequence (except 48 V).

POKB FAIL

Same as above.

POKC FAIL

Same as above.

POKD FAIL

Same as above.

POKE FAIL

The System Controller detects a power supply fault. The condition is logged but no power-off sequence is initiated.

BRD/CHASSIS OVR TEMP

The System Controller detects an over-temperature condition and initiates a power-off sequence.

POWER FAIL WARNING

The System Controller detects an AC power failure.

NO SYSTEM CLOCK

The System Controller could not detect a system clock on the backplane/midplane, and initiates a power-off sequence.

1.5V OVER VOLTAGE

The System Controller detects a power supply fault and initiates a power-off sequence. The System Controller will not turn power on until the operator selects “MENU - System Log.” This process guards against overvoltage damage by forcing the operator to examine the System Event Log.

5VDC OVER VOLTAGE

Same as above.

12VDC OVER VOLTAGE

Same as above.

-5.2VDC OVER VOLTAGE

Same as above.

-12VDC OVER VOLTAGE

Same as above.

48VDC OVER VOLTAGE

Same as above.

1.5VDC UNDER VOLTAGE

The System Controller detects a power supply fault and initiates the power-off sequence.

12VDC UNDER VOLTAGE

Same as above.

-5.2VDC UNDER VOLTAGE

Same as above.

-12VDC UNDER VOLTAGE

Same as above.

48VDC UNDER VOLTAGE

Same as above.

1.5VDC HIGH WARNING

The System Controller detects a voltage out of range. The condition is logged but no power-off sequence is initiated.

1.5VDC LOW WARNING

Same as above.

5VDC HIGH WARNING

Same as above.

5VDC LOW WARNING

Same as above.

12VDC HIGH WARNING

Same as above.

12VDC LOW WARNING

Same as above.

-5.2VDC HIGH WARNING

Same as above.

-5.2VDC LOW WARNING

Same as above.

-12VDC HIGH WARNING

Same as above.

-12VDC LOW WARNING

Same as above.

48VDC HIGH WARNING

Same as above.

48 VDC LOW WARNING

Same as above.

POWER CYCLE

The System Controller receives a command to perform a power-off, followed by a power-on, from the System Controller serial port.


Table C-2. System Events—Delayed Power-Off

Error Message

Failure Area/Possible Solution

AMBIENT OVER TEMP

The System Controller detects an over-temperature condition. An alarm is sent to the CPU; five seconds later, the System Controller initiates the power-off sequence.

BLOWER A FAILURE

The System Controller detects a fan problem. An alarm is sent to the CPU; five seconds later, the System Controller initiates the power-off sequence (rackmount systems only).

BLOWER B FAILURE

Same as above (rackmount systems only).

BLOWER FAILURE

Same as above (deskside systems only).

BLOWER A RPM FAIL

The System Controller detects a fan not at speed. An alarm is sent to the CPU, five seconds later the System Controller initiates the power-off sequence (rackmount systems only).

BLOWER B RPM FAIL

Same as above (rackmount systems only).

BLOWER RPM FAILURE

Same as above (deskside systems only).

TEMP SENSOR FAILURE

The System Controller detects a temperature sensor with a reading so far out of range that the sensor is assumed to have failed. The condition is logged but no power-off sequence is initiated.

FP BUTTON STUCK

The System Controller detects a status panel button stuck in the depressed position. After a 30-second wait, the power-off sequence is initiated (the depressed button interferes with the System Controller's normal monitoring operation.


Table C-3. System Events—Informative

Error Message

Error Meaning

SYSTEM ON

The System Controller reports the power-on sequence completed.

SYSTEM OFF

The System Controller reports the power-off sequence completed.

SYSTEM RESET

The System Controller generates a backplane reset, due to menu selection or serial port request.

NMI

The System Controller generates a backplane NMI, due to menu selection.

SCLR DETECTED

The System Controller detects a backplane reset, then initiates the bootmaster arbitration process.

BOOT ERROR

System Controller bootmaster arbitration could not find any host CPU responding on the serial bus. The System Controller is not able to communicate with the host CPU. The host CPU may not be running or may continue to boot normally.

INVALID CPU COMMAND

The System Controller detects bad command syntax from the host CPU on the Serial Bus. The command is ignored.


Table C-4. Internal System Controller Error Messages

Error Message

Error Meaning

BAD ALARM TYPE

The firmware attempted to send an invalid alarm to the CPU.

BAD MSG: CPU PROCESS

The CPU or System Controller process received an invalid message.

BAD MSG: DISPLAY

The display process received an invalid message.

BAD MSG: POK CHK

The power ok check process received an invalid message.

BAD MSG: SEQUENCER

The sequencer process received an invalid message.

BAD MSG: SYS MON

The system monitor process received an invalid message.

BAD WARNING/ALARM

The routine that decodes alarm and warning messages detected an invalid message.

BAD WARNING TYPE

The firmware attempted to send an invalid warning to the CPU.

COP FAILURE

The Computer Operating Properly (COP) timer exceeded time limits. The System Controller firmware must write to a COP timer port before it times out. If the firmware exceeds the time allowed between writes to a COP port, an interrupt is generated. The System Controller firmware may have entered an endless loop.

COP MONITOR FAILURE

A Computer Operating Properly (COP) clock monitor failure was detected. The System Controller clock oscillator is operating at less than
10 KHz.

DEBUG SWITCH ERROR

The System Controller detected data corruption in the nonvolatile RAM debug switch location.

FP CONTROLLER FAULT

An error was detected in the front panel LCD screen control process.

FP READ FAULT

A read of the front panel status register did not complete successfully.

FREE MSG NODE ERROR

The free message node queue overflowed.

FREE TCB NODE ERROR

The free timer control block queue overflowed.

ILLEGAL OPCODE TRAP

The System Controller's microprocessor tried to execute an illegal instruction, probably because of a stack overrun followed by a process switch.

PULSE ACCU INPUT

An interrupt was detected on the pulse accumulator input port. The port is not used and an interrupt is treated as an error.

PULSE ACCU OVERFLOW

The pulse accumulator overflow port received an interrupt. This port is unused and the interrupt is treated as an error.

SPI TRANSFER

An interrupt was detected on the synchronous serial peripheral interface. This interface is not supported and the interrupt is treated as an error.

STACK FAULT PID 0–6

One of the seven stack areas used by a System Controller process overflowed its assigned boundaries.

TEMP SENSOR FAILURE

The System Controller detected an invalid measurement from the temperature sensor.

TIMER IN COMP 1

The timer input compare port received an interrupt. The port is not used and the interrupt is treated as an error.

TIMER OUT COMP 1–5

One of the five timer output compare ports received an interrupt. The port is not supported and the interrupt is treated as an error.

XMITTER 1 TIMEOUT

The System Controller's 1st UART experienced a failure.

XMITTER 2 TIMEOUT

The System Controller's 2nd UART experienced a failure.